БУАВР.1 control unit
Automatic transfer switch controller for an ATS with two inputs and one load
Purpose:
- БУАВР1 controls automatic transfer from the main supply to the standby supply and back on unacceptable phase-voltage deviation, phase asymmetry or imbalance, changed phase sequence, or loss of one or more phases in either the main or the standby network.
- БУАВР1 can be used in supply networks as part of:
- automatic transfer switching (ATS);
- emergency transfer switching.
- БУАВР1 monitors the state of the inputs, controls contactors and motor-driven circuit breakers, and shows input and output states.
- БУАВР1 is built to climatic version У, siting category 2 (ГОСТ 15150-69) and operates at −25 °C to +55 °C, relative humidity up to 80 % and atmospheric pressure of 650 to 800 mmHg.
- БУАВР1 is intended for use in a non-explosive atmosphere free of gases and vapours in concentrations that attack metal or insulation, and free of saturated water vapour and conductive dust.
- Resistance to external mechanical factors — ГОСТ 17516.1, group М6
- Permissible vibration: 1 to 35 Hz at up to 4 m/s².
- БУАВР1 is powered from the monitored network whenever voltage is present on one phase of either input. When used in an ATS built on motor-driven circuit breakers, a separate control supply is recommended.
- БУАВР1 connects directly to 0.4 kV networks.
- Connection to networks of 6 kV and above requires step-down transformers with a 100 V secondary (the БУАВР1 version with a 100 V input).